FinalCommercialUpgrade
Electrical Permit

#2025-101265 EP

Electrical Permit - Upgrade

📋 Project Description

PERMIT SCOPE OF WORK: ELECTRICAL SERVICE UPGRADE ¿ SINGLE PHASE (320A METERED) 1. SERVICE ENTRANCE AND METERING REMOVE EXISTING METER BASE AND OVERHEAD RISER. INSTALL NEW OVERHEAD SERVICE RISER WITH WEATHERHEAD AND MAST FOR SINGLE-PHASE SERVICE. INSTALL NEW 320A CONTINUOUS-RATED METER BASE COMPATIBLE WITH ONCOR/PEC AND AUSTIN ENERGY. 2. MAIN DISCONNECTS AND GUTTER INSTALL ONE 125-AMP SURFACE-MOUNTED SERVICE-RATED DISCONNECT. INSTALL ONE 200-AMP SURFACE-MOUNTED SERVICE-RATED DISCONNECT. INSTALL 4-FOOT METAL GUTTER (WIREWAY) MOUNTED ABOVE THE DISCONNECTS TO MANAGE INCOMING AND OUTGOING CONDUCTORS. 3. PANEL AND DISTRIBUTION EQUIPMENT REMOVE ALL EXISTING ELECTRICAL PANELS. INSTALL ONE NEW 200/225 AMP 42-SPACE INDOOR MAIN LUG PANEL SURFACE-MOUNTED. 4. GROUNDING AND BONDING INSTALL TWO 8-FOOT COPPER GROUND RODS CONNECTED WITH #4 COPPER WIRE TO ESTABLISH THE MAIN GROUNDING SYSTEM. INSTALL GAS BOND USING #4 COPPER 21¿40 FEET IN LENGTH FROM THE GAS LINE TO THE MAIN PANEL. INSTALL WATER BOND USING #4 COPPER FROM AN OUTDOOR HOSE BIB TO THE MAIN PANEL. 5. SURGE PROTECTION INSTALL A WHOLE-HOME SURGE PROTECTOR AT THE MAIN PANEL.

📍 Project Location

Job Site Address

706 NORTH BLUFF DR, Austin, TX

View on Google Maps

🔧 Work Details

Work Class
Upgrade
Permit Type
Electrical Permit
Permit Class
Commercial

👷 Contractor Information

📅 Timeline

Applied Date
N/A
Issued Date
Sep 24, 2025
Expiration Date
N/A
← Back to All Permits